| BUILDING SPECIFICATIONS |
| Green Mark Certification |
| Platinum |
| Overall size |
| Approximately 350,000 sq ft nett leaseable area of Prime Grade A office space |
| No. of office floors |
| 33 floors (Storey 4th to 38th) |
| Typical floor area (NLA) |
| Approximately 11,000 sq ft |
| Core-to-window depth |
| 16.45m |
| Raised floor |
| Raised floor in 600x600 mm module pressed steel top, lightweight concrete infill. Raised floor height L5-38 - 150mm |
| Floor loading |
| 3.5kN/sqm and 7.5kN/sqm for compactus loading along 1m width of core wall area |
| Curtain wall |
| Full height glass. Unitised aluminium system with double glazed low E heat strengthened glass |
| Total no. of car parking spaces |
| 326 lots, full ERP Electronic Parking System |
| Toilets |
| Male (2 cubicles and 3 urinals) and Female (3 cubicles), 1 Handicap and 1 Executive with shower |
| Pantry |
| 1 common pantry on each floor |
| Air-conditioning and mechanical ventilation |
| - Central chilled water air-conditioning system |
| - Office floor - chilled water AHU c/w ducting and diffusers |
| - Main office lift lobby - chilled water AHU c/w ducting and diffusers |
| - Mechanical ventilation to staircase, smoke stop and fire fighting lobbies and toilets |
| Security system |
| - 24 hour CCTV monitoring at all main entrances and exits |
| - Card Access Control for turnstile at 1st storey lift lobbies, controlled access for staircases. |
| Fire protection |
| Automatic sprinkler, wet riser system, hosereel system and fire alarm system |
| Lighting |
| Average 500 Lux for office at 0.8AFFL T5 flourescent light, metal reflector, high frequency ballast |
| Electricity supply and electricity loads |
| Dual feed for 22kV incoming power supply. Office - 40 Amp three phase neutral isolator normal source, 20 Amp three phase neutral isolator emergency source. (DB and switch socket outlets by tenant) |
| Computing earthing |
| Earth bar provided on every office floor |
| Standby generator |
| 33% of tenants' normal load |
| Spare riser space |
| Space in electrical riser from 4th to 7th storey for tenant cabling to tenant genset, subject to availability |
| Space reserved for tenants own generator set |
| Provided above 4th storey link bridge |
| Telecommunication |
| Telecommunication distribution block terminal provided at landlord's common riser (telephone points by tenant) & SCV cable ready |
| Other features |
| Large column-free floorplates, high security features: bomb blast protected & penthouse office |